Lucrări de reconstrucție și modernizare a iluminatului public stradal în s. Volintiri, r-nul Ștefan Vodă

Information about customer
Fiscal code/IDNO
Address
MD-4241, MOLDOVA, Ştefan Vodă, s.Volintiri, str. Pacii
Web site
---
The contact person
Full name
Igor Hincu
Contact phone
067100029
Purchase data
Date created
25 Oct 2024, 14:41
Date modified
4 Nov 2024, 12:00
Achizitii.md ID
21303031
CPV
45200000-9 - Lucrări de construcţii complete sau parţiale şi lucrări publice
Type of procedure
Open tender
Award criteria
The lowest price
Funding sources
Documents of the procurement procedure
deviz de cheltueli1.docx
Bidding Documents
-Deviz de cheltueli
25.10.24 14:41
caiet de sarcini volintiri (2).pdf caiet de sarcini volintiri (2).pdf
Bidding Documents
-Caiet de sarcini
25.10.24 14:41
deviz de cheltueli 2.docx
Bidding Documents
-Deviz de cheltuei
25.10.24 14:41
documentatia_standard_iluminat stradal.docx
Bidding Documents
-Documentatia standard
25.10.24 14:41
duae iluminat stradal.doc
Bidding Documents
-DUAE
25.10.24 14:41
Date:
28 Oct 2024, 15:43
Question's name:
M6 - 23W, P5 - 50W
Question:
rugam sa clarificati situatia, pentru situatiile de strazi e corect indicat pentru clasa M6 - 23W si pentru clasa P5 - 50w? pc. 4,2 din caiet de sarcini
Answer (29 Oct 2024, 08:29):
Da, este corect. Pentru P5 până la 50W determinat de distanța între puncte luminoase de 65m. Înălțimea de montare - până la 9m. Înălțimea de montare se va socoti corect. Pentru M6-până la 7m. Pentru P5 - până la 9m.
Date:
28 Oct 2024, 15:46
Question's name:
proiectul de executie
Question:
rugam sa fie plasat proiectul de executie pe platforma.
Answer (29 Oct 2024, 08:29):
Proiectul este voluminos și nu putem să-l încarcam. Vă apropiați la Primărie și îl examinați.
Date:
28 Oct 2024, 15:47
Question's name:
p5 - 65m
Question:
rugam sa prezentati informatii din proiectul unde este indicat ca distanta medie dintre piloni e de 65m (cerinta nr. 6, tabelul 1, pct. 4,3)
Answer (29 Oct 2024, 08:29):
Corpurile de iluminat vor fi instalate peste un stâlp, distanța de referință între puncte luminoase este considerată de 65m.
Date:
1 Nov 2024, 14:26
Question's name:
Distanta Intre corpuri de Iluminat
Question:
De ce distnata dintre corpuri de Iluminat Proiectate este asa de mare?65m
Answer (4 Nov 2024, 11:55):
Findcă corpurile au fost instalate peste un pilon, iar distanța dintr piloni în mediu este de 33m. Primăria nu dispune de mijloace financiare pentru a acopri toată suprafața.
Date:
5 Nov 2024, 09:23
Question's name:
p5 - 65m
Question:
Dvs rugam sa prezentat informatii din proiect care confirma ca corpul de iluminat propus face facta la 65m. Daca nu, atunci modificati cerintele si indicati pentru ce distanda dintr-e pilini sa facem calculele. Puteti instala corpurile si peste 10, asta nu inseamna ca e necesar sa indicat cerinte aberante. rugam sa ajustati distanta pentru a va putea oferta solutia corecta.
Answer (6 Nov 2024, 14:23):
Proiectul a fost elaborat în baza calculelor. Sarcina ofertantului este de a îndeplini cerințele specificațiilor tehnice solicitate în documentația de atribuire.
Date:
5 Nov 2024, 09:25
Question's name:
P5-65m
Question:
nici corp de 300W nu poate face fată la 65m distanda dintr-e piloni, pentru ca pe de o parte primit prea multă lumină sub pilon, iar pe de alta nu se acopera distanta. De aceea e nevoie de indicat informatii ce permite a face calcule, sau prezentati o confirmare din proiect ca corpul de 50W instalat la 9m cu distata dintre piloni la 65m face fata pentur tipul de strada p5
Answer (6 Nov 2024, 14:30):
Încercați să folosiți un corp de iluminat până la 50W așa cum a fost solicitat.Încercați să alegeți corp de iluminat cu distribuția intensității luminoase potrivite distanței între stâlpi solicitate. La proiectare au fost 3 variante și toate satisfăcătoare.
Date:
5 Nov 2024, 11:41
Question's name:
informatii inconsistente
Question:
AC a emis un raspuns la 29 oct 2024, 08:29 Da, este corect. Pentru P5 până la 50W determinat de distanța între puncte luminoase de 65m. Înălțimea de montare - până la 9m. Înălțimea de montare se va socoti corect. Pentru M6-până la 7m. Pentru P5 - până la 9m. Cu toate acestea Situatia 2 din tabelul 1, pct. 4.3. prevede alte caracteristici, asa cum sunt inaltime de montare 6,5-7 m, 6m latime drum, respectiv situatia 1 - inaltimea 8-9 m. Deci rugam respectuos oferirea unor informatii corecte si finale ce tin de sarcina tehnica emisa
Answer (6 Nov 2024, 14:33):
La evaluare se vor considera următoarele: Pentru Situația 1 M6-înălțimea de montare până la 6,5-7m. Pentru Situația 2 P5-până la8-9m.
Date:
6 Nov 2024, 19:56
Question's name:
extindeti termenul de depunere a ofertelor
Question:
tinand cont de deciziile intarziate luate de AC, solicitam sa extindeti termenul depunere a ofertelor.
Answer (7 Nov 2024, 08:34):
Perioada de depunere a ofertelor: 8 nov 2024, 14:33 - 13 nov 2024, 18:33
Date:
6 Nov 2024, 20:01
Question's name:
rugam sa fie oferite informatii verifice
Question:
rugam sa fie plasat fisierul cu calculele unde e demonstrat ca corpul de 50W instalat pe tipul de strata P5, cu ltimea drtumului de 6 m, distanta dintre piloni de 65 m si inaltimea de montare 9 m, retragere pilon de 1 m, consola de 0.5m si unghi de inclinare panal la 15 grade normativele pentru tipul dat sunt satisfacute. Inca o data plasam solicitarea de clarificare - consideram ca cerinta de 65 m este depasita. Ca urmare a acestui raspuns va informam in mod oficial ca fara prezentarea unei confirmari din proiect ca corpul de iluminat solicitat pentru tipul de strada P5 face fata cerintelor, ne rezervam dreptul de a contesta prezentul concurs in termen permis de lege incepand cu raspunsul la prezenta solicitare de clarificare. Normativele de constructie INTERZIC a insala corpuri de iluminat peste un pilon, este interzis de normative, iar normativele de iluminat nu permit asemenea situatii. Deci dvs. aveti o solciitare depasita si e nevoie sa o demostrati ca ea este conform normativelor solicitate. Plus la toate, cele ce le-ati indicat ca raspuns la la 06.11.2024 ora 14.33 e nevoie sa ajustati Caietul de sarcini volintiri (2). multumim
Answer (7 Nov 2024, 09:15):
Iluminat Public s. Volintiri 1 Descriere Calculele luminotehnice au fost executate conform: • Propunerea corpurilor de iluminat corespunzatoare situatiilor împărțite pe clase de iluminat conform descrierii de mai jos: • Situația 1- clasa de iluminat M6 – latimea drumului 6 m, asfalt. • Situația 2- clasa de iluminat P5 – latimea drumului 6 m, pietris. • Asigurarea nivelurilor luminotehnice care sa aibă valori egale sau superioare celor reglementate de standardul SM EN 13201-2:2017. Ne referim aici la nivelul de iluminat mediu, nivelurile de iluminat minim, uniformităţi generale, etc. • Asigurarea unui nivel minim al consumului de energie electrica, cu condiţia îndeplinirii tuturor cerinţelor de performanta luminotehnica. • Pentru clasa de iluminat M6: Densitatea consumului de energie kWh/m2 an - maxim 0,4; Puterea instalata – maximum 23 W. • Pentru clasa de iluminat P5: Densitatea consumului de energie kWh/m2 an - maxim 0,6; Puterea instalata – maximum 50 W. Iluminat Public s. Volintiri Fişa de date privind produsul 2 Philips - BGP307 LED69-4S/740 PSA DM12 Nr.articol BGP307I-752a47ffbf59-486b-8c97- 2e69df275ebc P 39.7 W ΦLampă 6900 lm ΦCorp de iluminat 6115 lm η 88.62 % Eficienţa luminoasă 154.2 lm/W CCT 4000 K CRI 70 ClearWay Gen2 enables you to enjoy the benefits of LED technology for urban lighting right from the start. This new second generation of the luminaire builds on the strengths of its predecessor and is designed to further minimize your Total Cost of Ownership. ClearWay Gen2 significantly improves the most important aspects of the street lighting experience compared to conventional urban lighting. Ideal for new streets and for renovating existing installations, this affordable range of urban ClearWay lighting solutions combines clean design, high-quality light with significant energy and maintenance savings. In short, ClearWay Gen2 means good quality light with all the added benefits of LED - energy savings and long lifetime. Offering more benefits, yet packaged in a thinner and lighter design, which makes it easier to install. CDIL polar Iluminat Public s. Volintiri Stradă 2 · Alternativă 2 Rezumat (până la EN 13201:2015) 3 Iluminat Public s. Volintiri Stradă 2 · Alternativă 2 Rezumat (până la EN 13201:2015) 4 Producător Philips Nr.articol BGP307I-752a47ffbf59-486b-8c97- 2e69df275ebc Nume articol BGP307 LED69- 4S/740 PSA DM12 Dotare 1x LED69-4S/740 P 39.7 W ΦLampă 6900 lm ΦCorp de iluminat 6115 lm η 88.62 % Iluminat Public s. Volintiri Stradă 2 · Alternativă 2 Rezumat (până la EN 13201:2015) 5 BGP307 LED69-4S/740 PSA DM12 (Pe o parte Jos) Distanţă stâlp 65.000 m (1) Înălţimea punctului de lumină 9.000 m (2) Ieşirea în consolă a punctului de lumină -0.508 m (3) Înclinare consolă 10.0° (4) Lungime consolă 0.500 m Număr anual de ore de funcţionare 4000 h: 100.0 %, 39.7 W Putere / traseu 594.8 W/km ULR / ULOR 0.00 / 0.00 Intensităţi luminoase max. Orice direcţie ce formează unghiul dat cu verticala în jos a corpurilor de iluminat instalate pentru utilizare. ≥ 70°: 812 cd/klm ≥ 80°: 283 cd/klm ≥ 90°: 5.88 cd/klm Clasă intensitate luminoasă Valorile intensităţii luminoase în [cd/klm] pentru calculul clasei intensităţii luminoase se referă la fluxul luminos al corpului de iluminat, conform EN 13201:2015. – Clasă index ornamente D.6 MF 0.85 Iluminat Public s. Volintiri Stradă 2 · Alternativă 2 Rezumat (până la EN 13201:2015)
Date:
6 Nov 2024, 21:01
Question's name:
pagina web si catalogul
Question:
Rugam sa ne clarificati - in ce masura pagina web a producatorului si catalogul de produs a lui este un document si se refera la un standard national sau european. Rugam sa ne informati in ce conditii produsul certificat ENEC (cel mai inalt grad de conformitate a produsului) certificat in limita de putere de exempu 10-20W el se incadreaza in cerinta solicitata daca producatorul are produs de 15W, iar dvs aveti in solicitare corp de 11W. SUPLIMENTAR. Art. 18 din Legea 131/2015 prevede ==Autoritatea contractantă va aplica criterii proporţionale de calificare și selecție raportate la obiectul contractului referitoare numai la: e) standarde de asigurare a calităţii. Art.22 - (1) În cazul aplicării unei proceduri pentru atribuirea unui contract de achiziții publice de bunuri, în scopul verificării capacităţii tehnice şi/sau profesionale a ofertanţilor/candidaţilor, autoritatea contractantă are dreptul de a le solicita acestora, în funcţie de specificul, de cantitatea şi de complexitatea bunurilor ce urmează să fie furnizate şi numai în măsura în care aceste informaţii sînt relevante pentru îndeplinirea contractului și nu sînt disponibile în bazele de date ale autorităților publice sau ale părților terțe, următoarele: d) certificate sau alte documente emise de organisme abilitate în acest sens, care să ateste conformitatea bunurilor, identificată clar prin referire la specificaţii sau standarde relevante; Articolul 23. Standarde de asigurare a calităţii - se vorbeste doar de certificari .Articolul 37. (7) Specificaţiile tehnice se vor baza pe standardele naționale și internaţionale, pe reglementările tehnice şi normativele naţionale, după caz. Solicitare de Clarificare. Rugam sa indicati unde in Legea 131/2015, documentatia standard sau alta hotarare e specificat ca un produs plasat sau nu pe pagina we, existent sau neexistent in catalogul de produse respecta sau nu respecta anumite standarde. SUPLIMENTAR. Articolul 37. Regulile privind descrierea bunurilor, lucrărilor şi serviciilor (13) Un mijloc adecvat de a dovedi conformitatea cu specificaţiile tehnice solicitate îl poate reprezenta dosarul tehnic al producătorului sau un raport de încercare/testare emis de un organism recunoscut, cum ar fi, după caz, un laborator neutru de încercări şi calibrare sau un organism de certificare şi inspecţie care asigură respectarea standardelor naţionale/europene aplicabile. Autoritatea contractantă are obligaţia de a accepta certificate emise de organisme recunoscute în oricare dintre statele membre ale Uniunii Europene. IN acest articol nu se gasim ici o informatie ce tine de pagina web, catalog de produse. Se face referinta la Un dosar tehnic (adica certificatul de conformitate pe produs, insotit de rapoarte). Deci reiteram. In baza la ce este indicata solicitarea abuziva?
Answer (7 Nov 2024, 09:26):
AC are tot dreptul de a solicita produse standarde, alese de producător pentru întroducere pe piață,pînă la solicitarea ofertantului,întocmește documentația tehnică și asigură aplicarea procedurilor de evaluare a conformității, asigură corectitudinea și veridicitatea declarației de conformitate,deținerea rapoartelor de încercări,certificatelor de conformitate. Cu scop de a evita riscurile de evaluare la produsele modificate. AC nu are posibilități de evaluare profundă, numai comparativă.
Date:
7 Nov 2024, 10:20
Question's name:
Standarde de referinta
Question:
AC are obligatia de a respecta legea achizitiilor publice si a solicita acele documente si informatii in corespundere cu norme, standarde si reglemetari. Deci inca o data, rugam sa faceti referintala Standardul care va oferta dreptul de a solicita link la pagina web, catalog de produse, si toate aberatiile scrise.
Answer (8 Nov 2024, 08:31):
Conform proiectului
Date:
7 Nov 2024, 13:17
Question's name:
Certificat ENEC sau certificat echivalent si Declaratia de Calitate
Question:
Rugam sa ne clarificați, oe va prezenta un certficat ENEC care are un nivel de credibilitate superior oricăror declaratii de calitate de la producator pe proprie raspundere. Care este esența acestei declarații în condițiile în care Certificatul ENEC înlătură orice neclarități privitotoare la calitatea produsului ofertat ?
Answer (8 Nov 2024, 08:32):
Conform proiectului
Date:
7 Nov 2024, 13:21
Question's name:
Testul termic
Question:
Rugam sa ne explicați. Testul termic este un test efectuat pentru corpul de ilumina care confirmă că un produs asamblat în forma sa, duce la încălzirea sursei de lumina (LED-ului) la temperatura X. Atat. Acesta este un test unde se cunoaște temperatura. Durata sursei de lumina si confirmarea ei o face PRODUCATORUL sursei LED (exemplu OSRAM). Rugam sa ne oferiți detalii, ce fel de test termic solicitati, in condițiile cand testul termic al corpului de ILUMINAT nu reflecta durata lui de viata.?
Answer (8 Nov 2024, 14:27):
Conform proiectului
Only authorized platform users may ask questions during the clarification period.